Fire Watch Requirements: When a Fire Watch Is Required and What the Officer Does
Fire watch requirements under the International Fire Code, NFPA 101 and OSHA: what triggers a fire watch, what the officer does and what the log records.

Fire watch requirements put trained people on patrol when a building has lost fire protection it normally depends on, or when work on site creates a fire risk that equipment alone will not catch. The rules come from the International Fire Code (IFC) as adopted locally, NFPA standards, federal workplace safety rules for welding and cutting, and the conditions set by the local fire official.
The Two Most Common Triggers
Most fire watches start for one of two reasons.
1. A required fire protection system is out of service. A sprinkler system shut down for repairs, a fire alarm panel that has failed, a fire pump under maintenance, or a system damaged by a leak or a vehicle strike all leave a building without protection it was designed to have. The fire code treats this as an impairment and requires the owner to act.
2. Hot work is being performed. Welding, cutting, brazing, grinding and other spark or flame producing work can start fires that smolder for some time before anyone notices. Workplace safety rules require a dedicated fire watcher in many of these situations, both during the work and for a set period after it ends.
What the International Fire Code Requires When Systems Are Impaired
In the 2021 IFC, the governing section is Section 901.7, “Systems out of service.” Section numbers can differ in other editions and in state or local versions of the code, so the adopted text controls. Under that section, where a required fire protection system is out of service, the fire department and the fire code official must be notified. Where the fire code official requires it, the building must either be evacuated or an approved fire watch must be provided. The fire watch continues until the system is returned to service.
The code adds several supporting duties for the building owner:
- Impairment coordinator (901.7.1). The owner must assign an impairment coordinator. Where no one is designated, the owner is the impairment coordinator.
- Tag required (901.7.2). A tag must be used to show that a system, or part of one, has been removed from service.
- Placement of tag (901.7.3). The text reproduced by local fire officials lists the tag locations as each fire department connection, system control valve, fire alarm control unit, fire alarm annunciator and fire command center, with the fire code official specifying placement.
- Preplanned impairments (901.7.4). Planned shutdowns must be authorized by the impairment coordinator, and a list of steps must be completed before work begins.
- Emergency impairments (901.7.5). Unplanned failures require emergency action to limit injury and damage, followed by the same steps used for preplanned work.
- Restoring systems to service (901.7.6). When the equipment is back in working order, the coordinator must verify that the system works, notify the fire department and the other parties involved, and then remove the impairment tag.
The 2021 IFC text reproduced by the Matanuska-Susitna Borough also provides an exception for facilities with an approved notification and impairment management program. For water based systems, that program must comply with NFPA 25, the standard for inspection, testing and maintenance of water based fire protection systems.
Where NFPA Fits In
Many jurisdictions, health care regulators and insurers also rely on NFPA 101, the Life Safety Code. A tool published by the American Society for Health Care Engineering quotes the 2012 edition of NFPA 101, Section 9.6.1.6: where a required fire alarm system is out of service for more than 4 hours in a 24-hour period, the authority having jurisdiction must be notified, and the building must be evacuated or an approved fire watch provided for the parties left unprotected by the shutdown. The same tool notes that NFPA 101 (2012), Section 9.7.6, requires sprinkler impairment procedures to comply with NFPA 25 (2011).
The edition in force depends on what the state, city or regulator has adopted, so a property manager should confirm it with the local fire official.
Fire Watch for Hot Work
For general industry workplaces, the federal standard is OSHA 29 CFR 1910.252. It requires fire watchers whenever welding or cutting is performed in locations where other than a minor fire might develop, or where any of the following conditions exist:
- Appreciable combustible material, in building construction or contents, is closer than 35 feet to the point of operation.
- Appreciable combustibles are more than 35 feet away but are easily ignited by sparks.
- Wall or floor openings within a 35-foot radius expose combustible material in adjacent areas, including concealed spaces in walls or floors.
- Combustible materials are next to the opposite side of metal partitions, walls, ceilings or roofs and are likely to be ignited by conduction or radiation.
Under the same standard, fire watchers must have fire extinguishing equipment readily available and be trained in its use. They must be familiar with the facilities for sounding an alarm, watch for fires in all exposed areas, and try to put out a fire only when it is clearly within the capacity of the equipment available. Otherwise, they sound the alarm. A fire watch must be maintained for at least a half hour after welding or cutting is complete to detect and put out possible smoldering fires.
Facility hot work programs often build on this. A 2007 fire watch guideline published by the University of Colorado Boulder calls for the fire watch to continue for at least 30 minutes after cutting is complete, with areas that sparks or flame may have reached searched for signs of combustion. The hot work permit for the specific job remains the reference point.
What a Fire Watch Officer Does
Local fire departments publish their own procedures, and they overlap on the core duties. Drawing on the published guidance of the Charlotte Fire Department, the City of Aurora, Illinois, the Matanuska-Susitna Borough in Alaska, and the American Society for Health Care Engineering, a fire watch officer is expected to:
- Make fire watch the only job. Charlotte’s guidance states that the fire watch’s only duty is to perform constant patrols of the unprotected premises and keep watch for fires. Aurora requires one person assigned to the fire watch with that as the sole duty during the period. Charlotte also states that security personnel cannot serve as the fire watch if they also have security responsibilities, so additional staff may be needed.
- Patrol on a set schedule. Charlotte requires patrols of all unprotected areas at least once per hour. The Matanuska-Susitna Borough requires a complete walkthrough of the facility every hour.
- Be able to call the fire department. Charlotte requires at least one approved means of notifying the fire department, and Aurora requires at least one method of contacting the fire department in an emergency.
- Watch for hazards and keep exits clear. The ASHE procedure lists searching for fires, correcting hazards right away, controlling ignition sources, keeping exits clear and warning occupants if evacuation is needed.
- Keep an extinguisher at hand. The ASHE procedure calls for the fire watch to be trained in extinguisher use and to have an extinguisher accessible at all times.
What the Fire Watch Log Should Record
The log is the record that the fire watch took place. Published local forms point to a consistent set of entries:
- Facility name, address and an on site contact with phone number
- Date, and whether the watch covers a sprinkler impairment or a fire alarm impairment
- For each round, the exact time the round started and the areas patrolled
- The name and signature of the person who made the round
- Comments on hazards found, actions taken and any calls made
Charlotte’s guidance calls for a checklist showing which area was patrolled, who patrolled it and when. The Matanuska-Susitna Borough form provides an hourly line for the start time, signature and comments, and requires the completed form to be sent to the fire marshal’s office each morning while the watch is in effect. ASHE advises keeping the fire watch record available for inspection by the authority having jurisdiction.
How Local Fire Officials Set Conditions
The IFC gives the fire code official broad discretion, and local practice varies widely. Common conditions include:
- Deciding between evacuation and fire watch. Under Section 901.7, the official may require either evacuation or an approved fire watch. Charlotte’s guidance, written under the North Carolina State Fire Code, states that if a fire watch cannot be put in place, or the impairment coordinator cannot be reached, the fire official may order the building evacuated.
- Setting the trigger. Aurora, for example, requires a fire watch for an occupied building whose required fire protection system is out of service for more than 4 hours.
- Specifying tag locations. Charlotte’s guidance notes that the code official specifies where the out of service tag is placed.
- Ending the watch. Under Section 901.7, the fire watch runs until the system has been returned to service. A property manager should confirm with the local fire official whether any further sign off is expected.
Requirements in large cities can differ from the model code. Local fire departments in New York City and Los Angeles, for example, maintain their own rules and procedures, and a property manager should confirm them directly before scheduling coverage. Local summaries are available on the New York City fire watch and Los Angeles fire watch pages.
Frequently Asked Questions
Is a Fire Watch Required Every Time a Sprinkler or Alarm System Goes Down?
Not always. Under IFC Section 901.7, notification is required whenever a required system is out of service, and a fire watch or evacuation is required where the fire code official requires it. NFPA 101 (2012) sets a 4-hour in 24-hour threshold for fire alarm outages. Local officials may set their own triggers.
Can a Building’s Regular Security Officer Also Serve as the Fire Watch?
Charlotte’s published guidance says security personnel cannot serve as the fire watch if they also have security responsibilities, and Aurora requires the fire watch to be the person’s only duty. The local fire official decides.
How Long Does a Fire Watch Last After Hot Work?
OSHA 29 CFR 1910.252 requires at least a half hour after welding or cutting is complete. Permit programs and local codes may require longer.
How Often Must a Fire Watch Officer Patrol?
Charlotte requires patrols of unprotected areas at least once per hour, and the Matanuska-Susitna Borough requires an hourly walkthrough. The local fire official may set a different interval.
Fire Watch Coverage
For coverage during system impairments, renovations or hot work, see the McCray fire watch security service, which explains how McCray staffs and documents fire watch assignments.
Sources
- Charlotte Fire Department, FPB 214.02 Fire Watch Requirements and Procedures: https://www.charlottenc.gov/files/sharedassets/city/v/1/public-safety/fire/documents/fpb-214.02-fire-watch-requirements-and-procedures.pdf
- City of Aurora, Illinois, Fire Prevention Bureau, Fire Watch Requirements: https://publicsafety.aurora.il.us/Fire/Fire-Prevention-Bureau/Commercial-Prevention/Fire-Watch-Requirements
- City of Syracuse, New York, Fire Prevention Bureau, Fire Protection System Out of Service, Code Requirements: https://www.syr.gov/Departments/Fire/Fire-Prevention-Bureau/FireProtectionSystemOOS/Codes-Requirements
- Matanuska-Susitna Borough, Fire Watch Log Sheet (2021 IFC): https://matsugov.us/docs/general/22400/Fire-Watch-Log-Sheet–2021-IFC.pdf
- American Society for Health Care Engineering, Fire Watch Procedure Tool: https://www.ashe.org/system/files/media/file/2020/10/FireWatchProcedure-ASHE-Tool.pdf
- OSHA, 29 CFR 1910.252, Welding, Cutting and Brazing, General Requirements: https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.252
- University of Colorado Boulder, Fire and Life Safety, Hot Work Guideline: https://www.colorado.edu/firelifesafety/media/8
Planning coverage for a store, office or event? Call (833) 832-6647 or request a security assessment.